 +===== Modbus =====
 +
 +
 +----
 +
 +
 +Solar Monitor uses open communication protocol Modbus SunSpec, which meets requirements of [[https://sunspec.org/|SunSpec Alliance]]standard.\\ 
 +\\ 
 +Positive: fast communication
 +
 +
 +Negative: communication isn't secured
 +
 +
 +<WRAP info> Maximum number of clients who can send requests to Solar Monitor at the same time is 2 clientsl. </WRAP> In default setting of SM2-MU Modbus is disabled.\\ 
 +{{  :en:sim:manual:menu_nastaveni:modbus_zakazan.png?direct&  }}\\ 
 +\\ 
 +Enable Modbus\\ 
 +{{  :en:sim:manual:menu_nastaveni:modbus_nastaveni.png?direct&  }}\\ 
 +**Port** \\ 
 +Port for device communication. In default setting there is port 502 (same for TCP or UDP). This port works with packets. Modbus device address is a part of packet. You can change it if you need.\\ 
 +\\ 
 +**Power control** \\ 
 +Select here, which tool will control the output:\\ 
 +//No//- power wil be controlled by SM2-MU via module [[:en:sim:manual:rozsirujici_moduly:sm2_pc|SM2-PC]].\\ 
 +//Yes//- <font 12.8px/arial;;#000000;;#ffffff>power wil be controlled via</font> Modbus protocol.\\ 
 +\\ 
 +**Regime** \\ 
 +Type of network communication.\\ 
 +//TCP// - max. 2 TCP channels, i.e. only  PLC devices can be connected at the same time\\ 
 +//UDP// - any number of PLC or programmes can communicate via UDP protocole (e.g. Tecomat Foxtrot)\\ 
 +//UDP & TCP// - only 1 TCP channel and any number of PLC or programmes via UDP protocol\\ 
 +\\ 
 +When you have saved your choice, communication opens at the port.\\ 
 +\\ 
 +Modbus communication can be displayed in application [[http://sunspec.org/download‐sunspec‐dashboard/|SunSpec Dashboard]] (more info and installation conditions to be found [[https://sunspec.org/sunspec-dashboard/|here]]).\\ 
 +\\ 
 +__Example:__ \\ 
 +In Solar Monitor's web interface we can see these devices detected.\\ 
 +{{  :en:sim:manual:menu_nastaveni:sm_detected_devices.png?direct&  }}\\ 
 +In SunSpec Dashboard app click on bookmark //Device// and then //Open//.\\ 
 +{{  :en:sim:manual:menu_nastaveni:dashboard.png?direct&  }}\\ 
 +\\ 
 +A window with access parameters settings to Solar Monitor will open.\\ 
 +Fill in //IP Address//with Solar Monitor address. Fill in //Slave ID//with number of detected device (e.g. inverter). {{  :en:sim:manual:menu_nastaveni:open_device.png?direct&  }}\\ 
 +Application will search the inverter and display blocks which will show values of parameters. Supported versions enable also writing the values.\\ 
 +<WRAP half column> </WRAP> <WRAP half column> {{  :en:sim:manual:menu_nastaveni:common.png?direct&  }}</WRAP> <WRAP half column> {{  :en:sim:manual:menu_nastaveni:inverter.png?direct&  }}</WRAP> <WRAP half column> {{  :en:sim:manual:menu_nastaveni:controls.png?direct&  }}\\ 
 +</WRAP> <WRAP half column> {{  :en:sim:manual:menu_nastaveni:mppt.png?direct&  }}\\ 
 +</WRAP> If you want to read the parameters repeatedly, click on //Read // button on dashboard.\\ 
 +For recording values, click on //Write//.
 +=== How to add a file with more definitions of  ak přidat složku s další definicí modelu SunSpec (SMDX) ===
 +
 +
 +V aplikaci SunSpec Dashboard klikněte na záložku //Tools// a poté na //Model Directories//.\\ 
 +{{  :en:sim:manual:menu_nastaveni:dashboard_tools.png?direct&  }}\\ 
 +Klikněte na tlačítko //Add…// a v počítači vyhledejte složku se soubory smdx.\\ 
 +{{  :en:sim:manual:menu_nastaveni:add_directories.png?direct&  }}\\ 
 +Klikněte na OK.\\ 
 +Složka bude přidána do vyhledávací cesty informačního modelu.
  