 ===== SM2-PC ===== ===== SM2-PC =====
 +
 +
 ---- ----
-PC module (Power Control) controls your PV plant'​s power production. PV plant automatically adjusts its production according to purchaser'​s (ČEZ, E.ON, etc.) requirements. PC module can control both active and reactive power production.\\ ​+ 
 + 
 +PC module (Power Control) controls your PV plant'​s power production. PV plant automatically adjusts its production according to purchaser'​s (ČEZ, E.ON, etc.) requirements. PC module can control both active and reactive power production.\\ ​ 
 \\  \\ 
-{{  :​en:​sim:​manual:​rozsirujici_moduly:​moduly_vykres.png?​nolink |}} 
-\\ \\ \\ \\ 
-**Technická specifikace** \\ \\ 
-^Binární vstupy ​ |  2 x 5 vstupů s běžným Vcc a GND| 
-^  ^  ^ 
-|  |  | 
-^Svorky ​ |  max. průměr 1,5 mm?| 
-^  ^  ^ 
-|  |  | 
-^Připojení ​ |  HBUS| 
-^  ^  ^ 
-|  |  | 
-^Rozměry ​ |  36 x 89,7 x 62,2 mm| 
-^  ^  ^ 
-|  |  | 
-^Instalace ​ |  DIN lišta| 
-^  ^  ^ 
-|  |  | 
-^Napájení ​ |  12 – 24 V DC, max. 100 mA| 
-^  ^  ^ 
-|  |  | 
-^Teplotní rozsah ​ |  -25 °C to +60 °C| 
-\\ \\ 
 **Power control signals wiring** \\  **Power control signals wiring** \\ 
 \\  \\ 
 Signal DC- has to be connected to ACOM and BCOM terminals in order to control the power. Signal DC+ has to be connected to the multiple terminal of power control source (net operator'​s device). Power control signals are connected to terminals A1-A5 to control active power in % and to terminals B1-B5 to control reactive power (cos φ). The following picture shows sample scheme of active power control wiring in 0 - 30 - 60 - 100%.\\ ​ Signal DC- has to be connected to ACOM and BCOM terminals in order to control the power. Signal DC+ has to be connected to the multiple terminal of power control source (net operator'​s device). Power control signals are connected to terminals A1-A5 to control active power in % and to terminals B1-B5 to control reactive power (cos φ). The following picture shows sample scheme of active power control wiring in 0 - 30 - 60 - 100%.\\ ​
 \\  \\ 
-{{  ​:​en:​sim:​manual:​rozsirujici_moduly:​pc-pripojeni_signalu.png?​nolink&​500 ​ }}\\ +{{  ​.:​pc-pripojeni_signalu.png?​nolink&​500 ​ }}\\ 
 \\  \\ 
 **Start and configuration** \\  **Start and configuration** \\ 
Line 36: Line 17:
 As soon as the modules are connected and Solar Monitor unit is connected to the power supply, a green LED diode indicating status should glow. In case it doesn'​t glow, check if module is connected to SM2-MU. Open menu "​System set up / Power control"​ in you browser. You have to set up inputs combinations and relevant power control values in % or cos φ here.\\ ​ As soon as the modules are connected and Solar Monitor unit is connected to the power supply, a green LED diode indicating status should glow. In case it doesn'​t glow, check if module is connected to SM2-MU. Open menu "​System set up / Power control"​ in you browser. You have to set up inputs combinations and relevant power control values in % or cos φ here.\\ ​
 \\  \\ 
-{{  ​:​en:​sim:​manual:​rozsirujici_moduly:​pc-spusteni_a_konfigurace.png?​nolink& ​ ​}}\\ ​+{{  ​.:​pc-spusteni_a_konfigurace.png?​direct ​ ​}}\\ ​
 If you wish to use PC module for more Solar Monitor units, select option "​Remote"​ in menu "Power control source"​ for each unit. Fill in the address of SM2-MU, where the power control module is connected. .\\  If you wish to use PC module for more Solar Monitor units, select option "​Remote"​ in menu "Power control source"​ for each unit. Fill in the address of SM2-MU, where the power control module is connected. .\\ 
 \\  \\ 
-{{  :en:sim:​manual:​rozsirujici_moduly:pc-vzdaleny_modul.png?​nolink& ​ }} +{{  ​.:pc-vzdaleny_modul.png?​direct ​ }} 
 +\\ \\ 
 +{{ .:vzdalene_ovladani_vykonu.png?​direct |}} 
 +\\ \\ 
 +==== The example how to connect the SM2-MU to PLC Tecomat Foxtrot by Teco ==== 
 +__Connection__ 
 +{{ .:pc-foxtrot_sm_pc.png?​direct |}} \\ \\ 
 +__Configuration for 32 values of power control__ 
 +{{ .:​32_stupnu_rizeni_vykonu.png?​direct |}} 
 +\\ \\ 
 +==== Specification ==== 
 +<WRAP half column>​ 
 +^Binary inputs |  2 x 5 inputs with usual Vcc a GND | 
 +^  ^  | 
 +|  |  | 
 +^Terminals |  max diameter 1,5 mm? | 
 +^  ^  | 
 +|  |  | 
 +^Connectivity |  HBUS | 
 +^  ^  | 
 +|  |  | 
 +^Dimensions |  35.6 x 89.7 x 62.2 mm | 
 +^  ^  | 
 +|  |  | 
 +^Installation |  DIN rail | 
 +^  ^  | 
 +|  |  | 
 +^Power supply |  12 – 24 V DC, max 100 mA | 
 +^  ^  | 
 +|  |  | 
 +^Degree of protection |  IP20 | 
 +^  ^  | 
 +|  |  | 
 +^Temperature range |  -25 °C to +60 °C | 
 +</​WRAP>​ 
 +<WRAP half column>​ 
 +{{  .:​moduly_vykres.png?​nolink& ​ }} 
 +</​WRAP>​