Line 5: Line 5:
  
  
-PC module (Power Control) controls your PV plant'​s power production. PV plant automatically adjusts its production according to purchaser'​s (ČEZ, E.ON, etc.) requirements. PC module can control both active and reactive power production.\\ ​+PC module (Power Control) controls your PV plant'​s power production. PV plant automatically adjusts its production according to purchaser'​s (ČEZ, E.ON, etc.) requirements. PC module can control both active and reactive power production.\\ ​ 
 \\  \\ 
-{{  :​en:​sim:​manual:​rozsirujici_moduly:​moduly_vykres.png?​nolink& ​ }}\\ +**Power control signals wiring** ​\\ 
 \\  \\ 
 +Signal DC- has to be connected to ACOM and BCOM terminals in order to control the power. Signal DC+ has to be connected to the multiple terminal of power control source (net operator'​s device). Power control signals are connected to terminals A1-A5 to control active power in % and to terminals B1-B5 to control reactive power (cos φ). The following picture shows sample scheme of active power control wiring in 0 - 30 - 60 - 100%.\\ ​
 \\  \\ 
 +{{  .:​pc-pripojeni_signalu.png?​nolink&​500 ​ }}\\ 
 \\  \\ 
-**Specification** \\ +**Start and configuration** \\  
 +\\  
 +As soon as the modules are connected and Solar Monitor unit is connected to the power supply, a green LED diode indicating status should glow. In case it doesn'​t glow, check if module is connected to SM2-MU. Open menu "​System set up / Power control"​ in you browser. You have to set up inputs combinations and relevant power control values in % or cos φ here.\\  
 +\\  
 +{{  .:​pc-spusteni_a_konfigurace.png?​direct ​ }}\\  
 +If you wish to use PC module for more Solar Monitor units, select option "​Remote"​ in menu "Power control source"​ for each unit. Fill in the address of SM2-MU, where the power control module is connected. .\\  
 +\\  
 +{{  .:​pc-vzdaleny_modul.png?​direct ​ }} 
 +\\ \\ 
 +{{ .:​vzdalene_ovladani_vykonu.png?​direct |}} 
 +\\ \\ 
 +==== The example how to connect the SM2-MU to PLC Tecomat Foxtrot by Teco ==== 
 +__Connection__ 
 +{{ .:​pc-foxtrot_sm_pc.png?​direct |}} \\ \\ 
 +__Configuration for 32 values of power control__ 
 +{{ .:​32_stupnu_rizeni_vykonu.png?​direct |}} 
 +\\ \\ 
 +==== Specification ==== 
 +<WRAP half column>
 ^Binary inputs |  2 x 5 inputs with usual Vcc a GND | ^Binary inputs |  2 x 5 inputs with usual Vcc a GND |
 ^  ^  | ^  ^  |
Line 21: Line 41:
 ^  ^  | ^  ^  |
 |  |  | |  |  |
-^Dimensions |  ​36 x 89,7 x 62,2 mm |+^Dimensions |  ​35.6 x 89.7 x 62.2 mm |
 ^  ^  | ^  ^  |
 |  |  | |  |  |
Line 28: Line 48:
 |  |  | |  |  |
 ^Power supply |  12 – 24 V DC, max 100 mA | ^Power supply |  12 – 24 V DC, max 100 mA |
 +^  ^  |
 +|  |  |
 +^Degree of protection |  IP20 |
 ^  ^  | ^  ^  |
 |  |  | |  |  |
 ^Temperature range |  -25 °C to +60 °C | ^Temperature range |  -25 °C to +60 °C |
- +</WRAP> 
- +<WRAP half column> 
-\\  +{{  .:moduly_vykres.png?​nolink& ​ }} 
-\\  +</​WRAP>​
-**Power control signals wiring** \\  +
-\\  +
-Signal DC- has to be connected to ACOM and BCOM terminals in order to control the power. Signal DC+ has to be connected to the multiple terminal of power control source (net operator'​s device). Power control signals are connected to terminals A1-A5 to control active power in % and to terminals B1-B5 to control reactive power (cos φ). The following picture shows sample scheme of active power control wiring in 0 - 30 - 60 - 100%.\\  +
-\\  +
-{{  :​en:​sim:​manual:​rozsirujici_moduly:​pc-pripojeni_signalu.png?​nolink&​500 ​ }}\\  +
-\\  +
-**Start and configuration** \\  +
-\\  +
-As soon as the modules are connected and Solar Monitor unit is connected to the power supply, a green LED diode indicating status should glow. In case it doesn'​t glow, check if module is connected to SM2-MU. Open menu "​System set up Power control"​ in you browser. You have to set up inputs combinations and relevant power control values in % or cos φ here.\\ ​ +
-\\  +
-{{  ​:​en:​sim:​manual:​rozsirujici_moduly:​pc-spusteni_a_konfigurace.png?​nolink& ​ }}\\  +
-If you wish to use PC module for more Solar Monitor units, select option "​Remote"​ in menu "Power control source"​ for each unit. Fill in the address of SM2-MU, where the power control module is connected. .\\  +
-\\  +
-{{  :​en:​sim:​manual:​rozsirujici_moduly:pc-vzdaleny_modul.png?​nolink& ​ }} +
- +
- +
-\\ +
en/sim/manual/rozsirujici_moduly/sm2_pc.1407333628.txt.gz · Last modified: 2014/08/06 16:00 by jitka