This shows you the differences between two versions of the page.
en:sim:manual:popis:parametry_zakladniho_modulu [2014/08/26 12:33] ondra |
en:sim:manual:popis:parametry_zakladniho_modulu [2017/08/10 09:56] (current) ondra |
||
---|---|---|---|
Line 3: | Line 3: | ||
---- | ---- | ||
- | + | ^Max. number of devices<sup>1</sup> ^ | | |
- | + | |SM2-MU Basic and SM2-MU Start |1 device<sup>1</sup> | | |
- | {{ .:sm2_vykres.png?nolink& }} | + | |SM2-MU 60 |6 devices<sup>1</sup> | |
- | + | |SM2-MU 300 |30 devices<sup>1</sup> | | |
- | + | |SM2-MU 1000 |100 devices<sup>1</sup> | | |
- | ^Local area network LAN | | | + | |
- | |Interface | RJ45 (100BASE-T)-100Mbit/s, compatible with networks 10/100/1000 Mbit/s | | + | |
- | |Protocols | HTTP, SOAP, DNS, UDP Setup, Telnet, ARP, ICMP, SMTP | | + | |
^ ^ | | ^ ^ | | ||
| | | | | | | | ||
- | ^Sensors | | | + | ^Supported devices<sup>1</sup> ^Ethernet or serial bus connected | |
- | |Interface | terminal, cores 0,5 mm² - 1,5 mm² | | + | |Communication |Ethernet (TCP), up to 3 serial ports | |
- | |Max. number | 10 sensors | | + | |Inverter protocols |AEG, Carlo Gavazzi, Danfoss, Delta, Diehl, Fronius, IBC Solar, Kaco, Kostal, Mastervolt, Morningstar, Omron, Pairan, Power‑One, Refusol, Riello UPS, Santerno, Satcon, Schneider‑Electric, Siemens, Siliken, SMA, Solarmax, Solutronic, Studer, Sungrow, Sunville, Sunways, Vacon, Xantrex | |
- | |Max. distance | 100 m | | + | |Meter protocols |ABB (REX521), Carlo Gavazzi (VMU-E/X), Fronius (Smart Meter), KMB (SMC-144, PA-144), Phoenix Contact (MA200/250), Schneider‑Electric (SEPAM, PM9), Yorix (GreenBonO), ZPA (IEC 62056-21) | |
^ ^ | | ^ ^ | | ||
| | | | | | | | ||
- | ^Inverters | | | + | ^Sensors ^Dallas 1-wire bus | |
- | |Interface | 2 x RS485 or 1 x RS422 (to be selected in software) | | + | |Interface |Screw terminals for 05 mm² - 15 mm² cores | |
+ | |Max. count |10 sensors | | ||
+ | |Max. distance |100 m, recommended max. cable length for daisy‑chained sensors with minimal trunk segments | | ||
+ | ^ ^ | | ||
| | | | | | | | ||
- | ^Max. number of inverters detected | | | + | ^Ethernet interface (LAN) ^ | |
- | |Solar Monitor Basic and Solar Monitor Start | 1 inverter | | + | |Interface |RJ45 (100BASE-T) -100Mbit/s, compatible with networks 10/100/1000 Mbit/s, auto MDIX | |
- | |Solar Monitor 60 | 6 inverters | | + | |Protocols |HTTP, SOAP, DNS, UDP Setup, Telnet, ARP, ICMP, SMTP, SNMP, Modbus | |
- | |Solar Monitor 300 | 30 inverters | | + | |
- | |Solar Monitor 1000 | 100 inverters | | + | |
^ ^ | | ^ ^ | | ||
| | | | | | | | ||
- | ^Termination | YES, half and full duplex | | + | ^RS485 / RS422 / RS232 ^ | |
+ | |Interfaces |2x RS485 or 1x RS422<sup>2</sup> | | ||
+ | | | | | ||
+ | | |__//piggy-back hardware options//__ <sup>3</sup> | | ||
+ | | |2x RS485 or 1x RS422 opto-isolated<sup>2</sup> | | ||
+ | | |1x RS485 + 1x RS232 | | ||
+ | | |1x RS485 + 1x RS232 opto-isolated | | ||
+ | | | | | ||
+ | | |//__SM2-BE extension module__ // | | ||
+ | | |1x RS232 + 1x RS485 surge protected<sup>4</sup> | | ||
+ | | | | | ||
+ | |Speed |300 .. 115.200 bps (software configurable)<sup>2, 5</sup> | | ||
+ | |Termination |Yes, both for half and full duplex, configurable with jumpers | | ||
^ ^ | | ^ ^ | | ||
| | | | | | | | ||
- | ^Expansion option | | | + | ^Inputs ^opto-electronically isolated | |
- | |Interface | HBUS | | + | |3x digital inputs (DI) |software configurable between dry contact or S0 pulse meter inputs (e.g. from electrometer) | |
- | |Usage | SM2-PC, SM2-AD, SM2-DI, SM2-GSM | | + | |Max. distance |30 m (depends on cable) | |
^ ^ | | ^ ^ | | ||
| | | | | | | | ||
- | ^Inputs (optoelektronicky oddělené) | | | + | ^Outputs ^ | |
- | |Interface | bus 0,5 mm² - 1,5 mm², 2 inputs, 1 electrometer SO connection | | + | |1x relay |32 V, 3 A, protected with power fuse | |
- | |Max. distance | 30m | | + | |
^ ^ | | ^ ^ | | ||
| | | | | | | | ||
- | ^Output | 1 x relay (32 V, 3 A), with power fuse | | + | ^Electrical parameters ^ | |
+ | |Power supply |9-35 V DC, typ. 1.2 W @ 12V | | ||
+ | |DI1, DI2, DI3 |8-80 V | | ||
+ | |1 Wire |Interface provides 5 V power supply, max. 350 mA, protected with 500 mA power fuse. | | ||
+ | |RS485 |Protected against transient voltages above 6.8V and against high currents with 10Ω resistors. Additional surge protection can be achieved with SM2-BE (bus extension) module with gas discharge tubes: | | ||
+ | | |Minimum DC Sparkover (100 V/s) 185 V | | ||
+ | | |Service life: | | ||
+ | | |150 operations 8/20 μs 250 A, 1.2/50, 500 V (IEC61643-21) | | ||
+ | | |20 operations 2/10 μs, 5 kV, 500 A | | ||
+ | | |2 operations 8/20 μs, 1 kA | | ||
^ ^ | | ^ ^ | | ||
| | | | | | | | ||
- | ^Mechanické údaje | | | + | ^Mechanical parameters ^ | |
- | |Dimensions | 71,6 x 89,7 x 62,2 mm | | + | |Dimensions |71.6 x 89.7 x 62.2 mm | |
- | |Operating temperature | 0 up to + 70 °C | | + | |Mounting |DIN rail | |
- | |LED diodes | Status, RS485, Sensors | | + | |Screw terminals |05 mm² - 15 mm² cable cores | |
+ | |Degree of protection |IP20 | | ||
+ | |Operating temperature |0 .. +70 °C | | ||
+ | |LED diodes |Status, RS485, Sensors | | ||
^ ^ | | ^ ^ | | ||
| | | | | | | | ||
- | ^Power parameters | | | + | ^Extension options | | |
- | |power supply | 9-24 V, max. 3W | | + | |Interface |HBUS (DIN rail, bottom pluggable, no external wires needed) | |
- | |DI1, DI2, DI3 | 8-80 V | | + | |Extension modules |[[..:rozsirujici_moduly:sm2_pc|SM2-PC]], [[..:rozsirujici_moduly:sm2_ad|SM2-AD]], [[..:rozsirujici_moduly:sm2_di|SM2-DI]], [[..:rozsirujici_moduly:sm2_gsm|SM2-GSM]], [[..:rozsirujici_moduly:sm2_be|SM2-BE]] | |
- | |1 Wire | max. cable lenght 100 m, ext. 5 V, max. 350 mA, with power fuse 500 mA | | + | |
- | |RS485 | | | + | |
+ | <sup>1 … A device represents an inverter, stringbox, MPP tracker, battery monitor, meter or any other device which can be detected on any serial bus or via ethernet communication. </sup> \\ | ||
+ | \\ | ||
+ | <sup>2 … Can be configured by software (web UI, XML). </sup> \\ | ||
+ | \\ | ||
+ | <sup>3 … Piggy-back functionality replaces the “2x RS485 or 1x RS422” interface. </sup> \\ | ||
+ | \\ | ||
+ | <sup>4 … SM2-BE is mutually exclusive to the SM2-GSM usage. 2x SM2-BE modules can be also used to extend the HBUS connection between SM2 modules. </sup> \\ | ||
+ | \\ | ||
+ | <sup>5 … Communication speeds are available according to selected device communication protocols. </sup> | ||
\\ | \\ | ||
+ | {{ :en:sim:manual:popis:sm2_vykres.png?nolink& }} | ||