User Tools

Site Tools


en:sim:rm:web_zarizeni:vstupy_a_mereni

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

en:sim:rm:web_zarizeni:vstupy_a_mereni [2014/08/28 14:42]
jitka
en:sim:rm:web_zarizeni:vstupy_a_mereni [2014/09/11 10:16] (current)
ondra
Line 1: Line 1:
-===== Inputs ​and Measurement ​=====+===== Inputs ​& Meters ​=====
  
  
Line 5: Line 5:
  
  
-In SM2-RM go to menu System Setup/​Inputs ​and Measurement.\\  +In SM2-RM go to menu System Setup/​Inputs ​& Meters.\\ 
-\\  +
-{{  :​en:​sim:​rm:​web_zarizeni:​vstupy_a_mereni_3citace.png?​nolink& ​ }}\\  +
-\\ +
 \\  \\ 
 +{{  .:​vstupy_a_mereni_3citace.png?​nolink& ​ }}\\ 
 ==== Input 1, Input 2, Input 3 ==== ==== Input 1, Input 2, Input 3 ====
  
Line 16: Line 14:
 Assign each input its function.\\ ​ Assign each input its function.\\ ​
 \\  \\ 
-If you assign input **Reading ​** function, it will read pulses.\\  +If you assign input **Counter ​** function, it will count pulses.\\  
-<WRAP info> You can erase pulse score by changing energy correction, by changing input function (Reader, Inactive) or by pressing a reset button for 4 sec. The reset button is at the top of the box bellow Status diode. You can use e.g. a paper clip to press the button. ​ </​WRAP>​ If you choose **Input** function, there will be value 1 or 2 (connected, disconnected) in "​Overview"​.\\ ​+<WRAP info> You can erase pulse score by changing energy correction, by changing input function (Reader, Inactive) or by pressing a reset button for 4 sec. The reset button is at the top of the box bellow Status diode. You can use e.g. a paper clip to press the button. </​WRAP>​ If you choose **Input** function, there will be value 1 or 2 (connected, disconnected) in "​Overview"​.\\ ​
 \\  \\ 
 In case there is no device connected, choose **Inactive**.\\ ​ In case there is no device connected, choose **Inactive**.\\ ​
 \\  \\ 
 **Name** \\  **Name** \\ 
-You can assign the input any name (e.g. electrometer,​ gas meter, door sensor...).\\ +You can assign the input any name (e.g. electrometer,​ gas meter, door sensor).\\ 
 \\  \\ 
 **Meter Type** \\  **Meter Type** \\ 
Line 30: Line 28:
 \\  \\ 
 **Number of Pulses per 1 (kWh, m³)** \\  **Number of Pulses per 1 (kWh, m³)** \\ 
-Fill in the number of pulses per a unit (kWh, m³), that your meter generates at the SO output. This information is stated at the meter'​s label or in its documentation. If  wrong number of pulses is entered, SM2-RM will show wrong production or consumption values.\\ ​+Fill in the number of pulses per a unit (kWh, m³), that your meter generates at the SO output. This information is stated at the meter'​s label or in its documentation. If wrong number of pulses is entered, SM2-RM will show wrong production or consumption values.\\ ​
 \\  \\ 
 It is essential that electro meter'​s pulse output is configured for delivery.\\ ​ It is essential that electro meter'​s pulse output is configured for delivery.\\ ​
Line 36: Line 34:
 <WRAP info> Default setting is reading pulses from the electro meter, value 1000 pulses per 1 kWh. If your electro meter shows a different number, change the setting. </​WRAP>​ <WRAP half column>​\\ ​ <WRAP info> Default setting is reading pulses from the electro meter, value 1000 pulses per 1 kWh. If your electro meter shows a different number, change the setting. </​WRAP>​ <WRAP half column>​\\ ​
 The number of impulses per 1 kWh is usually between 250-1000 imp/1kWh. In case there are 2 possible numbers of impulses at your electro meter, the lower number is usually the right one for the SO output.\\ ​ The number of impulses per 1 kWh is usually between 250-1000 imp/1kWh. In case there are 2 possible numbers of impulses at your electro meter, the lower number is usually the right one for the SO output.\\ ​
-The higher number tells you how often a LED diode at your electro meter switches on.  </​WRAP>​ <WRAP half column> {{  ​:en:sim:rm:​rychly_navod:​jak_na_to:​obrazek_elmeru.png?​100 ​ }}</​WRAP>​\\ ​+The higher number tells you how often a LED diode at your electro meter switches on. </​WRAP>​ <WRAP half column> {{  ​..:​rychly_navod:​jak_na_to:​obrazek_elmeru.png?​100 ​ }}</​WRAP>​\\ ​
 **In case you need to setup number of pulses other than 1000 per 1 kWh než 1000, it is essential to differentiate between direct and indirect measurement:​** ​ **In case you need to setup number of pulses other than 1000 per 1 kWh než 1000, it is essential to differentiate between direct and indirect measurement:​** ​
 ==== 1. Direct Measuring ==== ==== 1. Direct Measuring ====
  
  
-In the electro meter'​s label or documentation find out how many pulses per 1 kWh your electro meter generates at the SO output. Fill in this value into relevant box in SM2-RM menu.\\ +In the electro meter'​s label or documentation find out how many pulses per 1 kWh your electro meter generates at the SO output. Fill in this value into relevant box in SM2-RM menu. 
 + 
 ==== 2. Indirect Measuring ==== ==== 2. Indirect Measuring ====
  
Line 52: Line 52:
 \\  \\ 
 </​WRAP>​ <WRAP half column>​\\ ​ </​WRAP>​ <WRAP half column>​\\ ​
-{{  ​:en:sim:rm:​rychly_navod:​jak_na_to:​pocet_pulzu_pomer.png?​200 ​ }}\\ +{{  ​..:​rychly_navod:​jak_na_to:​pocet_pulzu_pomer.png?​200 ​ }}\\ 
 \\  \\ 
 \\  \\ 
Line 59: Line 59:
  
  
-**Meter'​s ​Correction ** \\ +**Meter Correction ** \\ 
 This box is used for initial setting up SM2-RM and pulse meter. Fill in current value of kWh or m³ that your meter displays.\\ ​ This box is used for initial setting up SM2-RM and pulse meter. Fill in current value of kWh or m³ that your meter displays.\\ ​
 \\  \\ 
Line 67: Line 67:
 \\  \\ 
 //Example of another input function:// \\  //Example of another input function:// \\ 
-{{  ​:​en:​sim:​rm:​web_zarizeni:​vstupy_a_mereni_vice_moznosti.png?​nolink& ​ }}+{{  ​.:​vstupy_a_mereni_vice_moznosti.png?​nolink& ​ }}
  
en/sim/rm/web_zarizeni/vstupy_a_mereni.1409229732.txt.gz · Last modified: 2014/08/28 14:42 by jitka