User Tools

Site Tools

This translation is older than the original page and might be outdated. See what has changed.

en:sim:manual:menu_nastaveni:vstupy_a_vystupy

This is an old revision of the document!


Inputs & Counters


Submenu Inputs & Counters enables setting up the inputs

Table default setting:

Input set up

Select input function
Solar Monitor has 3 inputs available. Each works as:

a) Input = binary input

The table shows current input status. Set up their required values.
If you want to receive input set-up notification, select the option of email or SMS when you change the input values (on/off).

b) Counter = counts pulses from meter (electrometer, gasmeter, watermeter)

When you select the Counter option , there is table Counter set-up above the table Inputs.

For more info on pulse number set-up see chapter ELectrometer.
In case of setting up wrong values, Solar Monitor cannot show correct production data.

If the counter doesn't count pulses, check cables and polarity of electrometer connection.

c) Input and Counter = counting from device detected on RS485, RS232, Ethernet + can be used as binary input too.

When you select the Input and Counter option, there is table Counter set-up above the table Inputs.

If you want to use this input as binary input too, set up the required value.

en/sim/manual/menu_nastaveni/vstupy_a_vystupy.1531126900.txt.gz · Last modified: 2018/07/09 11:01 by jitka